← Backflow review queue
Backflow assembly test · 9857 Ridgeview Trl
ApprovedFiled Jan 2, 2026 by Reese Fairley, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Jan 2, 2026
- Assembly type
- PVB
- Serial number
- K724767
- Size
- 1
- Test gauge serial
- G-5368
- Gauge calibration date
- Aug 15, 2025
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 143-10-01043
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9857 Ridgeview Trl
Owner: Logan Danner
Parcel 143-10-01043