← Backflow review queue
Backflow assembly test · 9846 Quarry Rd
ApprovedFiled Jul 4, 2026 by Alex Benton, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 4, 2026
- Assembly type
- RP
- Serial number
- K155664
- Size
- 1
- Test gauge serial
- G-6878
- Gauge calibration date
- Jan 7, 2026
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 3.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-72-01129
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9846 Quarry Rd
Owner: Jamie Vance
Parcel 001-72-01129