Alameda County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Bakery

Filed Nov 15, 2026 by Parker Kessler, Keystone Backflow Testing · filed from phone

Report

Date of service
Nov 15, 2026
Assembly type
RP
Serial number
K639454
Size
4
Test gauge serial
G-2533
Gauge calibration date
Feb 11, 2026
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-20-01211
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

2331 Turkey Hill Trl
Owner: Wexler Holdings LLC
Parcel 001-20-01211