← Backflow review queue
Backflow assembly test · Station Diner
ApprovedFiled Mar 27, 2025 by Sam Brandt, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Mar 27, 2025
- Assembly type
- RP
- Serial number
- A563767
- Size
- 1
- Test gauge serial
- G-3306
- Gauge calibration date
- Jul 15, 2024
- Check valve 1
- 4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-82-01288
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
9217 Cedar Hollow Way
Owner: Marsh Holdings LLC
Parcel 001-82-01288