Backflow assembly test · 2614 Turkey Hill Trl
ApprovedFiled Feb 18, 2026 by Rowan Okafor, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Feb 18, 2026
- Assembly type
- DC
- Serial number
- Z492332
- Size
- 3/4
- Test gauge serial
- G-8314
- Gauge calibration date
- Dec 22, 2024
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-26-01080
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2614 Turkey Hill Trl
Owner: Morgan Wexler
Parcel 001-26-01080