← Backflow review queue
Backflow assembly test · Riverside Market
ApprovedFiled Jul 5, 2023 by Riley Danner, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Jul 5, 2023
- Assembly type
- DC
- Serial number
- W186508
- Size
- 1 1/2
- Test gauge serial
- G-4245
- Gauge calibration date
- Sep 29, 2022
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-97-01042
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6072 Cedar Hollow Rd
Owner: Danner Holdings LLC
Parcel 001-97-01042