Backflow assembly test · 6375 Spring Branch Ct
ApprovedFiled Dec 21, 2024 by Alex Benton, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 21, 2024
- Assembly type
- RP
- Serial number
- Z767820
- Size
- 3/4
- Test gauge serial
- G-7606
- Gauge calibration date
- Aug 2, 2024
- Check valve 1
- 0.8 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-20-01261
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.