Backflow assembly test · 707 Orchard Ct

Approved

Filed Nov 26, 2024 by Sam Brandt, Ridge Backflow Testing · filed from phone

Report

Date of service
Nov 26, 2024
Assembly type
RP
Serial number
Z161731
Size
3/4
Test gauge serial
G-1954
Gauge calibration date
Oct 25, 2023
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 001-56-01257
  • RP relief valve must open at 2.0 psid or more.
  • Test gauge calibration is more than a year old.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.