← Backflow review queue
Backflow assembly test · 2792 Pine Knoll Way
ApprovedFiled Aug 8, 2026 by Sam Brandt, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Aug 8, 2026
- Assembly type
- RP
- Serial number
- K198876
- Size
- 1
- Test gauge serial
- G-7910
- Gauge calibration date
- Jun 5, 2025
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.6 psid
- Relief valve opened at
- 3.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-94-01224
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2792 Pine Knoll Way
Owner: Alex Danner
Parcel 001-94-01224