← Backflow review queue
Backflow assembly test · Crossroads Elementary School
ApprovedFiled Oct 5, 2025 by Alex Benton, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 5, 2025
- Assembly type
- RP
- Serial number
- W477285
- Size
- 4
- Test gauge serial
- G-7718
- Gauge calibration date
- Apr 23, 2025
- Check valve 1
- 5.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 001-14-01037
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6707 Quarry Rd
Owner: Ashby Holdings LLC
Parcel 001-14-01037