Backflow assembly test · Corner Diner
ApprovedFiled Jun 8, 2026 by Reese Benton, Summit Backflow Testing · filed from phone
Report
- Date of service
- Jun 8, 2026
- Assembly type
- RP
- Serial number
- K673080
- Size
- 1 1/2
- Test gauge serial
- G-3970
- Gauge calibration date
- Apr 22, 2026
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 009-81-01163
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.