Backflow assembly test · Maple Leaf Medical Offices

Approved

Filed May 8, 2025 by Reese Benton, Summit Backflow Testing · filed from phone

Report

Date of service
May 8, 2025
Assembly type
RP
Serial number
A905525
Size
1 1/2
Test gauge serial
G-4150
Gauge calibration date
Dec 5, 2024
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 009-95-01224
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.