← Backflow review queue
Backflow assembly test · 9027 Turkey Hill Dr
ApprovedFiled Jul 24, 2025 by Jamie Whitcomb, Northstar Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jul 24, 2025
- Assembly type
- RP
- Serial number
- Z563742
- Size
- 1
- Test gauge serial
- G-5520
- Gauge calibration date
- Oct 30, 2024
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-17-01104
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
9027 Turkey Hill Dr
Owner: Alex Hollins
Parcel 013-17-01104