← Backflow review queue
Backflow assembly test · 1093 Mill Creek Trl
ApprovedFiled Jun 8, 2025 by Morgan Ashby, Valley Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jun 8, 2025
- Assembly type
- RP
- Serial number
- A189377
- Size
- 3/4
- Test gauge serial
- G-5902
- Gauge calibration date
- Apr 13, 2025
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-13-01087
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1093 Mill Creek Trl
Owner: Reese Wexler
Parcel 013-13-01087