Backflow assembly test · Riverside Taqueria
ApprovedFiled Jul 12, 2024 by Blake Marsh, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Jul 12, 2024
- Assembly type
- RP
- Serial number
- W458472
- Size
- 1
- Test gauge serial
- G-3005
- Gauge calibration date
- Nov 4, 2023
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-92-01058
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
5191 Meadow Lark Ct
Owner: Calloway Holdings LLC
Parcel 013-92-01058