← Backflow review queue
Backflow assembly test · 6875 Cedar Hollow Ct
Needs reviewFiled Nov 19, 2026 by Parker Ashby, Northstar Backflow Testing · filed from phone
Report
- Date of service
- Nov 19, 2026
- Assembly type
- RP
- Serial number
- K252281
- Size
- 1
- Test gauge serial
- G-3511
- Gauge calibration date
- Mar 6, 2026
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-83-01007
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
6875 Cedar Hollow Ct
Owner: Alex Fairley
Parcel 013-83-01007