← Backflow review queue
Backflow assembly test · 6541 Ridgeview Rd
ApprovedFiled Aug 12, 2025 by Casey Benton, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Aug 12, 2025
- Assembly type
- DC
- Serial number
- Z798226
- Size
- 1
- Test gauge serial
- G-5915
- Gauge calibration date
- Mar 10, 2025
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-69-01063
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6541 Ridgeview Rd
Owner: Jordan Stroud
Parcel 013-69-01063