← Backflow review queue
Backflow assembly test · Golden Grill
ApprovedFiled Apr 29, 2026 by Casey Benton, Patriot Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Apr 29, 2026
- Assembly type
- RP
- Serial number
- A519888
- Size
- 1 1/2
- Test gauge serial
- G-7443
- Gauge calibration date
- Jul 16, 2025
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-11-01127
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
6463 Mill Creek Dr
Owner: Nguyen Holdings LLC
Parcel 013-11-01127