Backflow assembly test · 6170 Spring Branch Ln
ApprovedFiled Jun 14, 2026 by Riley Marsh, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 14, 2026
- Assembly type
- PVB
- Serial number
- W825368
- Size
- 3/4
- Test gauge serial
- G-3240
- Gauge calibration date
- Apr 15, 2026
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 017-43-01078
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.