El Dorado County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Car Wash

Approved

Filed Oct 28, 2025 by Avery Ashby, Summit Backflow Testing · filed from phone

Report

Date of service
Oct 28, 2025
Assembly type
RP
Serial number
K535176
Size
1 1/2
Test gauge serial
G-9877
Gauge calibration date
Jun 4, 2025
Check valve 1
8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 017-56-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2681 Laurel Ln
Owner: Ramirez Holdings LLC
Parcel 017-56-01296