Backflow assembly test · 9673 Turkey Hill Ct

Filed Nov 25, 2026 by Avery Wexler, Valley Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Nov 25, 2026
Assembly type
RP
Serial number
K259118
Size
3/4
Test gauge serial
G-1283
Gauge calibration date
Feb 16, 2026
Check valve 1
8.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 017-12-01153
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

9673 Turkey Hill Ct
Owner: Sam Calloway
Parcel 017-12-01153