El Dorado County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Corner Car Wash

Approved

Filed Sep 3, 2025 by Avery Wexler, Valley Backflow Testing · filed from phone

Report

Date of service
Sep 3, 2025
Assembly type
RP
Serial number
W511526
Size
2
Test gauge serial
G-3060
Gauge calibration date
May 18, 2025
Check valve 1
7.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 017-61-01003
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3963 Hickory Rd
Owner: Ashby Holdings LLC
Parcel 017-61-01003