Backflow assembly test · 1489 Laurel Rd

Approved

Filed Feb 3, 2024 by Avery Ashby, Summit Backflow Testing · filed from phone

Report

Date of service
Feb 3, 2024
Assembly type
RP
Serial number
W118598
Size
3/4
Test gauge serial
G-1507
Gauge calibration date
Jul 18, 2023
Check valve 1
3.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
4.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 017-89-01242
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.