El Dorado County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1489 Laurel Rd

Approved

Filed Mar 18, 2026 by Riley Marsh, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Mar 18, 2026
Assembly type
RP
Serial number
W118598
Size
3/4
Test gauge serial
G-1143
Gauge calibration date
Jan 27, 2026
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 017-89-01242
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

1489 Laurel Rd
Owner: Jordan Pruitt
Parcel 017-89-01242