Backflow assembly test · 8887 Meadow Lark Rd
ApprovedFiled Aug 16, 2026 by Parker Benton, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Aug 16, 2026
- Assembly type
- PVB
- Serial number
- W216673
- Size
- 3/4
- Test gauge serial
- G-1488
- Gauge calibration date
- Jan 8, 2026
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-71-01189
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8887 Meadow Lark Rd
Owner: Sam Pruitt
Parcel 025-71-01189