Backflow assembly test · 8680 Hickory Way
Needs reviewFiled Nov 20, 2026 by Drew Stroud, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Nov 20, 2026
- Assembly type
- RP
- Serial number
- K361885
- Size
- 1
- Test gauge serial
- G-8677
- Gauge calibration date
- Dec 23, 2025
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.3 psid
- Relief valve opened at
- 2.5 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-56-01092
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.