Backflow assembly test · 5058 Meadow Lark Ln
ApprovedFiled Nov 3, 2023 by Parker Benton, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Nov 3, 2023
- Assembly type
- RP
- Serial number
- W378063
- Size
- 3/4
- Test gauge serial
- G-9770
- Gauge calibration date
- Jun 6, 2023
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Benton, current on the service date
- All required fields present
- Address matches parcel 025-57-01239
- Readings in range, no flags
- Result: passing. Next due date resets when approved.