Backflow assembly test · 5058 Meadow Lark Ln
ApprovedFiled Dec 9, 2024 by Parker Benton, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Dec 9, 2024
- Assembly type
- RP
- Serial number
- W378063
- Size
- 3/4
- Test gauge serial
- G-8406
- Gauge calibration date
- Sep 20, 2024
- Check valve 1
- 8.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Benton, current on the service date
- All required fields present
- Address matches parcel 025-57-01239
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.