Backflow assembly test · 1309 Ridgeview Ln
ApprovedFiled Jun 3, 2026 by Avery Vance, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Jun 3, 2026
- Assembly type
- DC
- Serial number
- B110446
- Size
- 3/4
- Test gauge serial
- G-3639
- Gauge calibration date
- Mar 20, 2026
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 025-37-01182
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.