Backflow assembly test · 1338 Quarry Ln

Approved

Filed Jun 6, 2026 by Drew Stroud, Ridge Backflow Testing · filed from phone

Report

Date of service
Jun 6, 2026
Assembly type
RP
Serial number
A906810
Size
1
Test gauge serial
G-7771
Gauge calibration date
Jan 19, 2026
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Stroud, current on the service date
  • All required fields present
  • Address matches parcel 025-26-01329
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1338 Quarry Ln
Owner: Blake Calloway
Parcel 025-26-01329