← Backflow review queue
Backflow assembly test · 825 Meadow Lark Ct
ApprovedFiled Jul 24, 2026 by Parker Whitcomb, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Jul 24, 2026
- Assembly type
- DC
- Serial number
- Z550054
- Size
- 1
- Test gauge serial
- G-2601
- Gauge calibration date
- Jun 17, 2026
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 037-86-01045
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
825 Meadow Lark Ct
Owner: Hayden Stroud
Parcel 037-86-01045