Backflow assembly test · 4902 Cedar Hollow Ln
ApprovedFiled Sep 19, 2025 by Parker Whitcomb, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Sep 19, 2025
- Assembly type
- PVB
- Serial number
- K579735
- Size
- 3/4
- Test gauge serial
- G-9551
- Gauge calibration date
- Apr 22, 2025
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 037-57-01341
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.