Los Angeles County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Crossroads Taqueria

Approved

Filed Jun 1, 2025 by Hayden Pruitt, Heritage Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Jun 1, 2025
Assembly type
RP
Serial number
Z347544
Size
1 1/2
Test gauge serial
G-3839
Gauge calibration date
Oct 12, 2024
Check valve 1
5.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 037-98-01323
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1491 Hickory Way
Owner: Benton Holdings LLC
Parcel 037-98-01323