Backflow assembly test · Hilltop Self Storage
Needs reviewFiled Nov 25, 2026 by Parker Vance, Valley Backflow Testing · filed from phone
Report
- Date of service
- Nov 25, 2026
- Assembly type
- RP
- Serial number
- A925810
- Size
- 1 1/2
- Test gauge serial
- G-8835
- Gauge calibration date
- Oct 16, 2026
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 037-89-01073
- Readings in range, no flags
- Result: passing. Next due date resets when approved.