← Backflow review queue
Backflow assembly test · Blue Heron Grill
ApprovedFiled Aug 2, 2025 by Parker Vance, Valley Backflow Testing · filed from phone
Report
- Date of service
- Aug 2, 2025
- Assembly type
- RP
- Serial number
- K507066
- Size
- 1
- Test gauge serial
- G-3124
- Gauge calibration date
- Nov 25, 2024
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 037-66-01115
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
743 Cedar Hollow Ln
Owner: Ellery Holdings LLC
Parcel 037-66-01115