Backflow assembly test · 438 Hickory Way
ApprovedFiled Dec 11, 2025 by Drew Kessler, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Dec 11, 2025
- Assembly type
- RP
- Serial number
- Z411685
- Size
- 3/4
- Test gauge serial
- G-2454
- Gauge calibration date
- Mar 30, 2025
- Check valve 1
- 8.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 037-74-01053
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.