← Backflow review queue
Backflow assembly test · 7291 Ridgeview Trl
ApprovedFiled Jun 13, 2026 by Parker Ashby, Valley Backflow Testing · filed from phone
Report
- Date of service
- Jun 13, 2026
- Assembly type
- RP
- Serial number
- W827183
- Size
- 1
- Test gauge serial
- G-1039
- Gauge calibration date
- Feb 3, 2026
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Ashby, current on the service date
- All required fields present
- Address matches parcel 041-30-01297
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7291 Ridgeview Trl
Owner: Quinn Nguyen
Parcel 041-30-01297