Marin County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 9071 Orchard Ct

Approved

Filed Dec 2, 2023 by Parker Harlow, Valley Backflow Testing · filed from phone

Report

Date of service
Dec 2, 2023
Assembly type
RP
Serial number
W186518
Size
3/4
Test gauge serial
G-5911
Gauge calibration date
Aug 2, 2023
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-53-01078
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9071 Orchard Ct
Owner: Hayden Stroud
Parcel 041-53-01078