ApprovedFiled Nov 22, 2024 by Casey Fairley, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Nov 22, 2024
- Assembly type
- RP
- Serial number
- W186518
- Size
- 3/4
- Test gauge serial
- G-9480
- Gauge calibration date
- Oct 9, 2023
- Check valve 1
- 0.9 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2 psid
- Relief valve opened at
- 3.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-53-01078
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.