Mono County, CAReports, deadlines and notices in one place
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Self Storage

Approved

Filed Sep 3, 2025 by Shawn Nguyen, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Sep 3, 2025
Assembly type
RP
Serial number
K998195
Size
2
Test gauge serial
G-3361
Gauge calibration date
Dec 16, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
1.7 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Shawn Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 051-89-01147
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

6861 Laurel Trl
Owner: Stroud Holdings LLC
Parcel 051-89-01147