Backflow assembly test · 5663 Spring Branch Ct
ApprovedFiled Sep 2, 2026 by Shawn Nguyen, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 2, 2026
- Assembly type
- DC
- Serial number
- K471191
- Size
- 3/4
- Test gauge serial
- G-5187
- Gauge calibration date
- Jun 3, 2026
- Check valve 1
- 3.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-23-01235
- Readings in range, no flags
- Result: passing. Next due date resets when approved.