Backflow assembly test · Two Rivers Animal Hospital
ApprovedFiled Jul 1, 2023 by Shawn Nguyen, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 1, 2023
- Assembly type
- RP
- Serial number
- Z432179
- Size
- 2
- Test gauge serial
- G-2790
- Gauge calibration date
- May 21, 2023
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-62-01299
- Readings in range, no flags
- Result: passing. Next due date resets when approved.