Backflow assembly test · 1649 Mill Creek Dr
ApprovedFiled Nov 8, 2023 by Shawn Nguyen, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 8, 2023
- Assembly type
- RP
- Serial number
- K298514
- Size
- 3/4
- Test gauge serial
- G-4986
- Gauge calibration date
- Sep 8, 2022
- Check valve 1
- 5.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 1.7 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Shawn Nguyen, current on the service date
- All required fields present
- Address matches parcel 051-60-01093
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1649 Mill Creek Dr
Owner: Morgan Harlow
Parcel 051-60-01093