Backflow assembly test · Station Elementary School

Approved

Filed Mar 11, 2026 by Parker Nguyen, Heritage Backflow Testing · filed from phone

Report

Date of service
Mar 11, 2026
Assembly type
RP
Serial number
Z615892
Size
1
Test gauge serial
G-2331
Gauge calibration date
Aug 8, 2025
Check valve 1
3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 051-20-01186
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.