← Backflow review queue
Backflow assembly test · Golden Market
ApprovedFiled Oct 30, 2023 by Parker Nguyen, Heritage Backflow Testing · filed from phone
Report
- Date of service
- Oct 30, 2023
- Assembly type
- DC
- Serial number
- K529285
- Size
- 1 1/2
- Test gauge serial
- G-6377
- Gauge calibration date
- Jul 8, 2023
- Check valve 1
- 8.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-69-01269
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
5399 Fox Run Trl
Owner: Lindqvist Holdings LLC
Parcel 051-69-01269