Backflow assembly test · 8423 Meadow Lark Trl
Needs reviewFiled Nov 23, 2026 by Parker Nguyen, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 23, 2026
- Assembly type
- RP
- Serial number
- K662853
- Size
- 1
- Test gauge serial
- G-6534
- Gauge calibration date
- May 30, 2026
- Check valve 1
- 7.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-89-01029
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Property
8423 Meadow Lark Trl
Owner: Hayden Lindqvist
Parcel 051-89-01029