Backflow assembly test · 6699 Old Church Ln
ApprovedFiled Jun 23, 2025 by Parker Nguyen, Heritage Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jun 23, 2025
- Assembly type
- DC
- Serial number
- B640091
- Size
- 3/4
- Test gauge serial
- G-8280
- Gauge calibration date
- Oct 14, 2024
- Check valve 1
- 5.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 051-79-01132
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.