Backflow assembly test · 6194 Meadow Lark Dr
ApprovedFiled Jul 27, 2025 by Emerson Hollins, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 27, 2025
- Assembly type
- RP
- Serial number
- B959711
- Size
- 3/4
- Test gauge serial
- G-7758
- Gauge calibration date
- Sep 21, 2024
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 053-22-01300
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6194 Meadow Lark Dr
Owner: Quinn Brandt
Parcel 053-22-01300