Monterey County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7944 Cedar Hollow Ln

Approved

Filed Sep 12, 2026 by Parker Fairley, Patriot Plumbing & Backflow · filed from phone

Report

Date of service
Sep 12, 2026
Assembly type
RP
Serial number
B210315
Size
1
Test gauge serial
G-2690
Gauge calibration date
Mar 21, 2026
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
1.4 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 053-18-01334
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7944 Cedar Hollow Ln
Owner: Cameron Harlow
Parcel 053-18-01334