Backflow assembly test · Hilltop Apartments
ApprovedFiled Feb 28, 2025 by Cameron Kessler, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Feb 28, 2025
- Assembly type
- RP
- Serial number
- B322578
- Size
- 4
- Test gauge serial
- G-4751
- Gauge calibration date
- Aug 7, 2024
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 053-44-01130
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.